Preheating of Fresh Air : Fresco SL
Fresco SL : Solar Preheating on Flat Roofs
The Fresco SL solar air heater is designed for mounting on flat roofs to preheat outside air just before it enters the ventilation unit, with no impact on the building’s architecture.
Because it is mounted on spacious flat roofs, the Fresco’s major advantage over wall installations is that it can always be designed to face due South, and inclined at an optimal inclination of 70°, to maximize solar warm air output during the cold season.
How the Solar Collector Works
Technical Data
Technical Sheet
Fresco SL | SI Units [IP Units] |
---|---|
Technical Data | |
Solar air collector type | Transpired unglazed collector |
Working fluid | Air only |
Main use and purpose | Preheating of outdoor air |
Solar area | 6 m2 [65 ft2] |
Possible airflow range | 170 m3/h à 1000 m3/h [100 CFM à 600 CFM] |
Pressure drop @ maximum throughflow | 370 Pa [1 in H2O] |
Maximum temperature rise above ambient | 50 °C [90 °F] |
Peak solar efficiency, rated | 90 |
Weight | 40 kg [100 lbs] |
Absorber panel | |
Panel material | Aluminum alloy 99.8, Temper H18 |
Absorber panel thickness | 0.7 mm [0.028 in] |
Panel surface treatment | Highly selective VDP coating |
Available colors, selective | blue, black |
Absorbtivity in thermal spectrum | ≥94% |
Emissivity in thermal spectrum | ≤3% |
Panel porosity | 1-4% |
Mounted collector system | |
Typical distance between 2 rows* | 390 mm [15.3 in] |
Typical inclination to the horizontal | 70° |
Optimal orientation | Sud ou sud-est |
Minimal hieght of the collector above roofline | 900 mm [36 in] |
Required maintenance | none |
Freeze protection | N/A |
Overheating protection | N/A |
Ratings & certifications | |
Solar Rating Certification Corp. certificate no | SRCC 10002111 |
Test laboratory | Fraunhofer ISE, Germany |
*Note : Calculate at 45° of latitude |